APC Easy UPS On-Line SRV Ext. Runtime 2000VA 230V with External Battery Pack
Mã hàng: SRV2KIL
Xuất xứ: China
Bảo hành: 3 năm
THÔNG SỐ KỸ THUẬT SẢN PHẨM
|
Overview
|
Presentation
|
High quality, Double-conversion On-line UPS designed for essential power protection needs even in the most unstable power conditions.
|
Lead time
|
Usually in Stock
|
|
Main
|
Thời gian chạy cho tải
|
1600W
22phút 17giây
Tối thiểu-tối đa: 160-1600W
|
Công suất tối đa đã sử dụng
|
100 %
|
Main Input Voltage
|
230 V
|
Other Input Voltage
|
220 V
240 V
|
Main Output Voltage
|
230 V
|
Other Output Voltage
|
220 V
240 V
|
Rated power in W
|
1600 W
|
Rated power in VA
|
2000 VA
|
Input Connection Type
|
IEC 60320 C14
|
output connection type
|
4 IEC 60320 C13
|
Cable length
|
1.52 m
|
number of cables
|
1
|
provided equipment
|
1 IEC 60320 C13 to Schuko power cable
1 IEC 60320 C13 to C14 power cable
1 USB cable
1 RS-232 configuration cable
1 external battery pack
1 battery cable
user manual
|
|
General
|
Number of power module filled slots
|
0
|
Number of power module free slots
|
0
|
Redundant
|
No
|
|
Physical
|
colour
|
Black (RAL 7010)
|
Height
|
33.6 cm
|
width
|
33.5 cm
|
Depth
|
42.5 cm
|
Net weight
|
45.4 kg
|
mounting location
|
Front
|
mounting preference
|
No preference
|
mounting mode
|
Not rack-mountable
|
USB compatible
|
Yes
|
mounting position
|
Vertical
|
|
Input
|
input voltage limits
|
110...285 V half load
160...280 V full load
|
network frequency
|
40...70 Hz auto sensing
|
|
Output
|
Maximum configurable power in VA
|
2000 VA
|
Maximum configurable power in W
|
1600 W
|
output frequency
|
50/60 Hz +/- 3 Hz sync to mains
|
Harmonic distortion
|
3 %
|
UPS type
|
Double conversion online
|
Wave type
|
Sine wave
|
efficiency
|
88 % (full load)
|
Additional information
|
Configurable for 220 : 230 or 240 nominal output voltage
|
bypass type
|
Internal bypass (automatic and manual)
|
crest factor
|
3 : 1
|
|
Conformance
|
product certifications
|
CE
UKCA
EAC
TISI
|
standards
|
EN/IEC 62040-1:2019/A11:2021
EN/IEC 62040-2:2006/AC:2006
EN/IEC 62040-2:2018
|
|
Environmental
|
Ambient air temperature for operation
|
0…40 °C
|
relative humidity
|
0…95 % non-condensing
|
Operating altitude
|
0...3000 m
|
Ambient air temperature for storage
|
-20…50 °C
|
storage Relative Humidity
|
Non-condensing 0…95 %
|
Storage altitude
|
0…15000 m
|
Acoustic level
|
50 dBA
|
Heat dissipation
|
745 Btu/h
|
IP degree of protection
|
IP20
|
|
|